UPS systems

6 kVA online UPS, external battery

Model ES6000

Online double-conversion UPS rated 6 kVA / 5.4 kW with input power factor correction, for an external bank of 16, 18 or 20 batteries of 12 V.

Capacity
6 kVA / 5.4 kW
Type
Online, double conversion
Battery
External, 16 x 12 V (18 or 20 also supported)
Charger current
10 A (max.)

Overview

Highlights

  • 6 kVA / 5.4 kW online double-conversion UPS with input power factor correction and output power factor 0.9
  • External bank of 16, 18 or 20 x 12 V batteries, set as required, with a 10 A charger
  • Input range 120 to 276 V AC depending on load, input power factor 0.99, input THD under 3%
  • Up to four units can run in parallel through the optional parallel port
  • 0 ms transfer from mains to battery; up to 94% efficiency, 99% in ECO mode
  • RS232 and USB ports, EPO, maintenance switch and a slot for an optional SNMP card

It gives a pure sine wave output with ±1% voltage regulation, and up to four units can run in parallel.

At a glance

Type
Online
Capacity
6 kVA
Battery
External
Used with
Batteries and spike busters and surge protectors See products

Specifications

Power

Rated capacity
6 kVA / 5.4 kW
Topology
Online, double conversion, high frequency, with input power factor correction
Control
DSP digital control, IGBT inverter and rectifier, PWM
Phase
Single phase in, single phase out
Parallel operation
Up to 4 units (optional parallel port)
Isolation transformer
Optional
Form factor
Tower

Input

Input phase
Single phase with earth
Rated input voltage
220 / 230 / 240 V AC
Input voltage range
120 to 276 V AC, depending on load
Input frequency range
40 to 70 Hz
Input power factor
0.99 or higher
Input current distortion
THDi under 3%
Generator input
Supported

Output

Output voltage
220 / 230 / 240 V AC, set on the panel (220 V AC default)
Output power factor
0.9
Voltage regulation
±1%
Output frequency
±0.05 Hz, synchronised with the mains in AC mode
Crest factor
3:1
Harmonic distortion
2% THD or less (linear load)
Waveform
Pure sine wave
Overload capacity
105% to 110% for 1 hour, 110% to 125% for 10 minutes, 125% to 150% for 1 minute; above 150%, transfers to bypass immediately
Transfer time
0 ms mains to battery, 15 ms typical inverter to bypass
ECO mode
Supported, set on the LCD
Bypass output with the UPS off
Supported, set on the LCD
Efficiency
Up to 94% in double conversion mode, 99% in ECO mode

Battery

Battery
External
Number of batteries
16, 18 or 20 x 12 V, set as required
Battery voltage
192, 216 or 240 V DC with 16, 18 or 20 batteries
Charging current (max.)
10 A
Charge mode
Boost or float charge, switched automatically
Charging voltage
Depends on the number of batteries

Display, communication and protection

LCD
Input and output voltage and frequency, battery voltage, load in W, VA and %, inverter temperature, operating mode (online, on battery, bypass), fault codes, battery and load bar graphs
LED indicators
Normal operation, bypass abnormal, fault, battery mode
Protection
Over temperature, fan fault, output short circuit, low battery voltage, input over or under voltage, overload
Communication
RS232 standard; USB, external Modbus, SNMP card, RS-485 and dry contact optional
Other functions
Static bypass, cold start, auto restart, battery charging with the UPS off, EMI/RFI filter, solar compatible
Standards
IEC/EN 62040-1, 62040-2 and 62040-3, complies with CE and BIS
Certification marks
BIS R-41033642 (IS 16242 Part 1 / IEC 62040-1), CE, RoHS

Environment

Operating temperature
0 to 45 °C
Storage temperature
-25 to 55 °C
Relative humidity
0 to 95%, non-condensing
Altitude
Below 1500 m; derated above 1500 m

Physical

Dimensions (D x W x H)
480 x 220 x 438 mm
Net weight
18 kg
Rear panel
Intelligent slot for an SNMP card (optional), RS232, USB, EPO, fan, maintenance switch, parallel port (optional), wire harness mount, input breaker

Elnova battery bank bundles

15 min backup
16 x 12 Ah batteries with rack and interlinks
30 min backup
16 x 26 Ah batteries with rack and interlinks
60 min backup
20 x 42 Ah batteries with rack and interlinks
90 min backup
16 x 75 Ah batteries with rack and interlinks
120 min backup
16 x 100 Ah batteries with rack and interlinks
Load for these backup times
Not stated by Elnova

Warranty

Warranty
1 year

Specifications are taken from the manufacturer's published information and may change. Confirm critical values with our sales desk before ordering.

Elnova product page

Works with

Batteries for the external bank

Use the battery voltage and count the UPS specifies.

Spike busters and surge protectors

Support

Warranty and repairs

Warranty is as per Elnova’s terms for this model. For products bought from us, call our service team with the invoice number, the model and the product’s serial number.

From Elnova

Practical notes

  1. Charge a new UPS for the time stated in its manual before relying on it.
  2. Keep the UPS in a ventilated place away from heat, because battery life falls in hot rooms.
  3. Check the warranty terms for the UPS and for the battery, since they can differ.

Request a quote

Share the quantity and delivery location for ES6000. Our sales desk replies with price and availability, subject to stock.

You are a (optional)